Page 46
Delete work (Add 009)
The UMG96S has four work meters. Three ac-
tive power demand counters and one reactive
power demand counters.
User password (Add 011)
A user password can be programmed to make
it difficult for the programming data to be acci-
dentally changed. It is only possible to switch
to the subsequent programming menus after
the correct user password has been entered.
A default user password is not pre-assigned in
the factory. In this case the password menu is
skipped and the current transformer menu
opens immediately.
If a user password has been programmed the
password menu appears with the display “000”.
The first digit of the user password flashes and
can be changed using Key 2. If you press Key
1, the next digit is selected and flashes.
The programming menu for the current trans-
former only opens if the correct number combi-
nation has been entered.
If an altered user password is no longer re-
membered, the device must be sent to the
manufacturer.
The work meters can only be deleted jointly.
To delete the contents of the work meters, „001“
must be written in the Address 009.
Add Name
416 Total active power demand
(without return block)
418 Total reactive power demand (inductive)
422 Total active power demand
(imported or HT)
424 Total active power demand (supply or LT)