Page 76
Tables
Parameter list
The parameter list contains all the settings required for correct operation of the UMG96S, e.g.
current transformer and device address. The values in the parameter list can be written and read.
Data and time in address 700 are an exception and can only be written. The date and time in
seconds since 1.1.1970 can be read in address 410 of the measured value list.
Measured value list
The measured value list contains the measured and calculated measured values, status data of
the inputs and outputs and logged values for reading out.
Formats
CHAR
= 1 byte
INT
= 2 bytes; (high before low byte)
LONG
= 4 bytes; (high before low byte)
STRING1
= 32 byte; Byte 1=row 1, Bit1=1st meas. value table, Bit2=2nd meas.valuet able...
Byte 2=row 2, Bit1=1st meas. value table, Bit2=2nd meas. value table...
STRING2
= 6 bytes; hour,minute,second,day,month,year
FDATA
= 2 bytes; data record number
4 bytes; time since 1.1.1970
10 bytes; data string
1 byte; profile number
1 byte; error information
Display of CosPhi in the UMG96S
Measured value display
Measured value list and data memory
Analog outputs and switching con-
tacts
Capacitive
inductive
1,00
0.00cap
0.00ind
-100
-1
+100
+0
-100 +100
0 0
1,00 1,00
Important!
For several parameters, only the PC software
GridVis can utilise the maximum adjustment
range. Only values up to 999999 can be set at the UMG96S.