Page 20
Serial interfaces
The various design versions of the UMG96S
have up to two serial interfaces.
The serial interfaces are not isolated from each
other.
Inputs and outputs
In the various design versions (options) of the
UMG96S, different functions can be assigned
to the outputs.
For example, terminal 12 can be assigned to
the pulse output function and terminal 13 the
digital input function. Here it must be ensured
that both electric circuits have a common im-
ported supply via terminal 11 (+24V).
Only one function can ever be assigned to ter-
minal 12 and terminal 13.
12
13
11
Input/Output 2
Pulse output Wq (003 = 0)
Digital output
(003 = 1)
Analog output (003 = 2)
Digital input
(003 = 3.5)
Remote profibus (003 = 4)
Input/Output 1
Pulse output Wp (002 = 0)
Digital output
(002 = 1)
Analog output (002 = 2)
Digital input
(002 = 3.5)
Remote profibus (002 = 4)
Important!
Pulse output 1 is
permanently
assigned
to active power demand Wp.
Pulse output 2 is
permanently
assigned
to reactive power demand Wq.
m
m
The cables for serial data transfer must
be shielded.