Page 77
Add Name
Adjustm. range Type Units Default
000
UMG96S Device address
1 .. 255
CHAR
-
1
001
Baud rate (RS232 and RS485)
0 .. 2
CHAR
1)
kbps
0
002
Input/Output 1, type
0 .. 5
CHAR
2)
-
0
003
Input/Output 2, type
0 .. 5
CHAR
2)
-
0
004
Pulse value, digital output 1
0 .. 100000
PULSE
Wh
1.00
5)
006
Pulse value, digital output 2
0 .. 100000
PULSE
varh
1.00
5)
008
Delete min and max values
0 .. 1
CHAR
-
0
009
Delete work
0 .. 1
CHAR
-
0
010
Minimum pulse length, digital output 1/2
5 .. 99
CHAR
3)
ms
5=50ms
011
User password
0 .. 999
INT
-
000
012
LCD contrast
0 .. 7
CHAR
-
3
013
Comparator 1A, limit value
-999999999 ..
999999999
LONG
0
015
Comparator 1A, measured value
0 .. 999
INT
6)
000
016
Comparator 1A, minimum on-time
1 .. 899
INT
Sec.
1
017
Comparator 1A, operator
0, 1
CHAR
4)
0
018
Comparator 1B, limit value
-999999999 ..
999999999
LONG
020
Comparator 1B, measured value
0 .. 999
INT
6)
021
Comparator 1B, minimum on-time
1 .. 899
INT
Sec.
1
022
Comparator 1B, operator
0, 1
CHAR
4)
0
023
Comparator 1C, limit value
-999999999 ..
999999999
LONG
025
Comparator 1C, measured value
0 .. 999
INT
6)
026
Comparator 1C, minimum on-time
1 .. 899
INT
Sec.
1
027
Comparator 1C, operator
0, 1
CHAR
4)
0
028
Comparator 2A, limit value
-999999999 ..
999999999
LONG
030
Comparator 2A, measured value
0 .. 999
INT
6)
031
Comparator 2A, minimum on-time
1 .. 899
INT
Sec.
1
032
Comparator 2A, operator
0, 1
CHAR
4)
0
033
Comparator 2B, limit value
-999999999 ..
999999999
LONG
035
Comparator 2B, measured value
0 .. 999
INT
6)
036
Comparator 2B, minimum on-time
1 .. 899
INT
Sec.
1
037
Comparator 2B, do not invert/invert
0, 1
CHAR
4)
0
038
Comparator 2C, limit value
-999999999 ..
999999999
LONG
1) 0 = 9.6kBit/s; 1 = 19.2kBit/s; 2 = 38.4kBit/s
2)
0 = Pulse output , 1 = digital output , 2 = analog output, 3 = digital input,
4 = Profibus remote output, 5 = HT/LT switchover via a digital input.
3) minimum pulse length = set value * 10 [ms]
4) 0 = greater or equal to, 1 = smaller
5) When reading out /writing, 100 = 1.00
6) 0 = Comparator is not used, 1 = remote, 200-424 = measured values
Parameter list
Important!
For several parameters, only the PC software
GridVis can utilise the maximum adjustment
range. Only values up to 999999 can be set at the UMG96S.