Page 50
Serial interfaces
The various design versions of the UMG96S
have up to three serial interfaces.
Profibus DP
RS232
The serial interfaces are not isolated from each
other. The profibus interface can be run simul-
taneously with the RS232 interface.
Modem mode (Add 070)
An analog modem can be connected to the
UMG96S via the RS232 interface. In order for
the UMG96S to be able to transmit data via an
analog modem, the address 070 must be as-
signed the value 1.
Address 070 = 0 => Modem mode = No
Address 070 = 1 => Modem mode = Yes
The RS232 interface is connected with the ana-
log modem by a modem cable (option). The
modem cable, Product No. 08.01.503, is not in-
cluded in the scope of supply of the RS232 in-
terface (option).
Fig. Back of the UMG96S.
Device address (Add 000)
If several devices are connected to each other
via profibus interface, a master device (PC,
programmable controller) can only differentiate
between these devices by means of their de-
vice address. Therefore, each UMG96S within
a system must have a different device address.
Device addresses within the range 0 to 255 can
be set.
Profibus only uses device addresses within the
range 0 to 126.
Baud rate (Add 001)
A common baud rate can be set for the RS232
and RS485 interfaces.
Baud rate
: 9.6, 19.2 and 38.4kBit/s
Data bits
: 8
Parity
: none
Stop bits (UMG96S) : 2
Stop bits (external) : 1 or 2
DSUB -9
socket
RS232/Modbus
RTU
RJ11