Page 49
Software release (Add 913)
The software for the UMG96S is continuously
improved and enhanced. The software status in
the device is denoted with a 3-digit number, the
software release. The user cannot change the
software release.
Hardware configuration (Add 914)
The options available in the UMG96S can be
queried via the address 914. One bit is set for
each available option. This results in a binary
value which is displayed as a decimal number
by the UMG96S.
Example 1
The UMG96S displays the decimal value
96
at
Address 914.
Option
Hex
Binary
Name
0x01
0000 0001
Memory (EEPROM)
0x02
0000 0010
Clock
0x04
0000 0100
Analog output 1/2
0x08
0000 1000
Digital output or
Pulse output 1/2
0x10
0001 0000
Digital input 1/2
0x20
0010 0000
Profibus
0x40
0100 0000
RS232
0x80
1000 0000
RS485
Profibus option
RS232 option
96
= 0x60 = 0110 0000
Example 2
The UMG96S displays the decimal value
248
at Address 914.
Digital output 1/2
Digital input 1/2
Profibus
RS232
RS485
248
= 0xf8 = 1111 1000
Address =914
Value =
96
L1