Page 93
Auxiliary voltage
Voltage range
:18V .. 60V DC, 18V .. 30V AC 50/60Hz
Power input
:max. 1.4W, max. 2.6VA
Back-up fuse
: 2A. 10A (medium time lag)
Measurement
Measuring rate
:
1 measurement/sec.
Impulse voltage withstand level
:
4kV
Signal frequency
: 45Hz. 1000Hz
Voltage measurement
Frequency of the fundamental component
: 45Hz. 65Hz
Power input
: approx 0.1VA
Impedance
: 4MOhm per phase
300V
standard version
: max. 300V AC to earth
Measuring range L-N
: 50 .. 300V AC
Measuring range L-L
: 87 .. 520V AC
150V
special version
: max. 150V AC to earth
Measuring range L-N
: 25 .. 150V AC
Measuring range L-L
: 40 .. 260V AC
Current measurement
: max. 150VAC to earth
Power input
: approx 0.2 VA
Rated current at ../5A (../1A)
: 5A (1A)
Threshold current
: 5mA
Limit current at ../1A
: 1,2A (sinusoidal)
Limit current at ../5A
: 6A (sinusoidal)
Overload
: 150A for 2 sec.
Serial interfaces
RS232, RJ11 socket (option)
Protocol
: MODBUS RTU
Transmission rates
: 9.6, 19.2, 38.4kBit/s
RS485, DSUB-9 (option)
Protocol
: Profibus DP (V0)
Transmission rates
: 9.6, 19.2, 45.45, 93.75, 187.5, 500,
1500kBit/s
Connectable conductors
Solid core, multi-core, flexible core
: 0.08 - 2.5mm2
Pin-end connector, wire end ferrules
: 1.5mm2
Per terminal connection, only one conductor
may be connected!
Technical specifications Part 3
* The smallest operating voltage for devices with the Profibus option is 140V AC.