Page 24
Putting into Service
The UMG96S should be put into service as fol-
lows:
Installing the device
The UMG96S is intended for installation in low-
voltage distributions in which the maximum
overvoltages that occur are in overvoltage cat-
egory III.
It can be installed in any position. The enclosed
fixing brackets must be used to install the de-
vice in front panels or switchgear cabinet doors.
Applying the auxiliary voltage
The size of the auxiliary voltage is given on the
rating plate. Auxiliary voltages which do not cor-
respond to those given on the rating plate can
result in malfunctions and destruction of the
device.
After applying the auxiliary voltage, all seg-
ments appear in the display. Around two sec-
onds later the UMG96S switches to the first
measured value display.
If no display appears, check whether the auxil-
iary voltage is within the rated voltage range.
Switchboard
max. 6
9
0
9
6
49
D
S
U
B
-
9
1234
1234
1234
1234
1234
1234
1234
1234
1234
1234
1234
1234
1234
1234
42
6
2,5
R
J
1
1
Fixing bracket
Auxiliary section dimensions: 92
+0.8
x 92
+0.8
mm
RS 232
Uh I / O
UMG 96 S
45-65Hz 3VA
Made in Germany
S V J M A D E
P
Strommessung/Current Measurement
k
l
L2
L3
L1
k
l
k
l
5
7
10
8
9
N L3 L2 L1
6
Spannungsmessung
Voltage Measurement
15 14 13 12 11 4 3 2 1
Profibus