Page 60
Inputs and outputs
The terminals 12 and 13 at the UMG96S can
be optionally assigned the following functions:
0 = Pulse output,
1 = Digital output,
2 = Analog output (option),
3 = Digital input (option),
4 = Profibus remote output (option),
5 = HT/LT switchover via a
Digital input (option),
6 = Synchronisation of storage of
memory profile 1 via a
Digital input (option).
The required function (0..6) is written in the ad-
dress 002 corresponding to terminal 12 or ad-
dress 003 corresponding to terminal 13.
Input/Output 2 (003)
Pulse output Wq (003 = 0)
Digital output
(003 = 1)
Analog output (003 = 2)
Digital input
(003 = 3.5)
Remote profibus (003 = 4)
Input/Output 1 (002)
Pulse output Wp (002 = 0)
Digital output
(002 = 1)
Analog output (002 = 2)
Digital input
(002 = 3.5)
Remote profibus (002 = 4)
12
13
11
UMG96S
+
It is not possible to simultaneously use different
functions on one terminal. It is possible to si-
multaneously use different functions on differ-
ent terminals. In this case is must be ensured
that the common imported supply for terminals
12 and 13 is applied to terminal 11(+).
Possible input and output combinations:
a) 2 digital outputs,
b) 2 digital inputs,
c) 2 analog outputs,
d) 1 digital output and 1 analog output,
e) 1 digital output and 1 digital input.
Uh
Current measurement
1
5
1
4
1
3
1
2
1
1
1
0
8
7
9
1
3
2
4
6
5
I / O
Voltage
measurement