Page 96
Quick Reference Instructions
Changing the current transformer
Switching to programming mode
If you are in display mode and press Keys 1 and 2 for around
one second, you switch to programming mode.
The symbols for programming mode
PRG
and for the current
transformer CT appear.
Use Key 1 to confirm the selection.
The first line of the primary current flashes.
V
L1
L2
L3
K1
K2
1
2
PRG
k A
L1
L2
L3
CT
Primary current
Secondary current
1
2
Calling up the measured values
Switching to display mode
If you are in programming mode and simultaneously press
Keys 1 and 2 for around one second, you switch to display
mode.
The
PRG
symbol for programming mode is not in the display
and the first measured value display appears, e.g. for the
voltage.
Key 2
Press Key 2 to page between the various measured value dis-
plays for current, voltage, power output, etc.
Key 1
Use Key 1 to page between the mean values, max values,
etc. for the measured value.
Change primary current
Use Key 2 to change the flashing digit.
Use Key 1 to select the next digit to be changed.
The digit selected for changing flashes.
If the whole number flashes, the decimal point can be shifted.
Change secondary current
Only 1A or 5A can be set as the secondary current.
Use Key 1 to select the secondary current.
Use Key 2 to change the flashing digit.
Quit programming mode
Simultaneously press both keys for around 1 second.
The current transformer setting is saved and you return to dis-
play mode.
Current transformer
symbol
Programming mode
PRG
k A
L1
L2
L3
CT
1
2