Communication extension card
PROFIBUS communication card
-10-
Bit
Name
Value
State to be entered/description
consumption to zero
13
Pre-excitation
1
Enabling pre-excitation
0
Disabling pre-excitation
14
DC braking
1
Enabling DC braking
0
Disabling DC braking
15
Heartbeat reference
1
Enabling heartbeat
0
Disabling heartbeat
Reference value (REF): The second to twelfth words in a PZD task packet are the main
settings. The main frequency settings are provided by the main setting signal source. Table
2-6 describes the settings of Goodrive350 series VFD.
Table 2-6 Settings of Goodrive350 series VFD
Function
code
Word
Value range
Default
value
P15.02
Received
PZD2
0: Invalid
1: Set frequency (0–Fmax, unit: 0.01 Hz)
2: PID reference (0–1000, in which 1000 corresponds to
100.0%)
3: PID feedback (0–1000, in which 1000 corresponds to
100.0%)
4: Torque setting (-3000–+3000, in which 1000
corresponds to 100.0% of the rated current of the
motor)
5: Setting of the upper limit of forward running
frequency (0–Fmax, unit: 0.01 Hz)
6: Setting of the upper limit of reverse running
frequency (0–Fmax, unit: 0.01 Hz)
7: Upper limit of the electromotive torque (0–3000, in
which 1000 corresponds to 100.0% of the rated current
of the motor)
8: Upper limit of the brake torque (0–3000, in which
1000 corresponds to 100.0% of the rated current of the
motor)
9: Virtual input terminal command, 0x000–0x3FF
(corresponding to S8, S7, S6, S5, HDIB, HDIA, S4, S3,
S2, and S1 in sequence)
10: Virtual output terminal command, 0x00–0x0F
(corresponding to RO2, RO1, HDO, and Y1 in
sequence)
11: Voltage setting (for V/F separation)
0
P15.03
Received
PZD3
0
P15.04
Received
PZD4
0
P15.05
Received
PZD5
0
P15.06
Received
PZD6
0
P15.07
Received
PZD7
0
P15.08
Received
PZD8
0
P15.09
Received
PZD9
0
P15.10
Received
PZD10
0
P15.11
Received
PZD11
0
P15.12
Received
0