Communication extension card
EtherNet/IP communication card
-66-
Function
code
Word
Value range
Default
value
PZD2
1: Running frequency (×100, Hz)
2: Set frequency (×100, Hz)
3: Bus voltage (×10, V)
4: Output voltage (×1, V)
5: Output current (×10, A)
6: Actual output torque (×10, %)
7: Actual output power (×10, %)
8: Rotating speed (×1, RPM)
9: Linear speed (×1, m/s)
10: Ramp frequency reference
11: Fault code
12: AI1 value (×100, V)
13: AI2 value (×100, V)
14: AI3 value (×100, V)
15: HDIA frequency (×100, kHz)
16: Terminal input state
17: Terminal output state
18: PID reference (×100, %)
19: PID feedback (×100, %)
20: Motor rated torque
21: MSB of position reference (signed number)
22: LSB of position reference (unsigned number)
23: MSB of position feedback (signed number)
24: LSB of position feedback (unsigned number)
25: State word
26: HDIB frequency value (×100, kHz)
P16.44
Transmitted
PZD3
0
P16.45
Transmitted
PZD4
0
P16.46
Transmitted
PZD5
0
P16.47
Transmitted
PZD6
0
P16.48
Transmitted
PZD7
0
P16.49
Transmitted
PZD8
0
P16.50
Transmitted
PZD9
0
P16.51
Transmitted
PZD10
0
P16.52
Transmitted
PZD11
0
P16.53
Transmitted
PZD12
0
PKW zone
PKW zone (parameter identification flag PKW1––numerical zone): The PKW zone describes
the processing mode of the parameter identification interface. A PKW interface is not a
physical interface but a mechanism that defines the transmission mode (such reading and
writing a parameter value) of a parameter between two communication ends.
Parameter
identification (PKW)
Process data
PKW1
PKW2
PKW3
PKW4
CW
SW
PZD2
PZD2
Request
No.
Response
No.l
Parameter
address
Parameter
value error
No.
Parameter
value
Figure 5-6 Parameter identification zone