Communication extension card
Related function codes
-125-
Function
code
Name
Parameter description
Setting
range
Default
value
P16.17
Ethernet
monitoring
variable address
4
0x0000–0xFFFF
0000–FF
FF
0x0000
P16.18
EtherCAT
communication
timeout time
0.0 (invalid)–300.0s
0.0–300.
0s
0.5s
P16.19
Reserved
P16.20
MSD of BACnet
device number Independent code of BACnet device
(0–4194303)
0–4194
0
P16.21
LSD of BACnet
device number
0–999
1
P16.22
BACnet "I-Am"
service setting
0: Transmission at power-on
1: Continuous transmission
0–1
0
P16.23
BACnet
communication
timeout time
0.0 (invalid)–300.0s
0.0–300.
0
0.0s
P16.24
Extension card
identification
time of slot 1
0.0–600.0s
When this parameter is set to 0.0,
identification fault detection is not
performed.
0.0–600.
00
0.0
P16.25
Extension card
identification
time of slot 2
0.0–600.0s
When this parameter is set to 0.0,
identification fault detection is not
performed.
0.0–600.
00
0.0
P16.26
Extension card
identification
time of slot 3
0.0–600.0s
When this parameter is set to 0.0,
identification fault detection is not
performed.
0.0–600.
00
0.0
P16.27
Extension card
communication
timeout time of
slot 1
0.0–600.0s
When this parameter is set to 0.0,
disconnection fault detection is not
performed.
0.0–600.
00
0.0
P16.28
Extension card
communication
timeout time of
slot 2
0.0–600.0s
When this parameter is set to 0.0,
disconnection fault detection is not
performed.
0.0–600.
00
0.0