Communication extension card
EtherNet/IP communication card
-78-
Note:
The ring network monitoring function can be used only when the PLC is in
programming mode.
Click
Advanced...
and then set DLR parameters (such as
Beacon Interval
and
Beacon Timeout
) in the window that appears.
Note: When there are four or less EtherNet/IP slaves, you are recommended to set
Beacon Interval
to 400μs and
Beacon Timeout
to 4000μs. When there are ten or
less but more than four EtherNet/IP slaves, you are recommended to set
Beacon
Interval
to 6000μs and
Beacon Timeout
to 18000μs. Set parameters depending on
the actual situation.
Содержание Goodrive350 Series
Страница 1: ......
Страница 104: ...Communication extension card EtherCAT communication card 99...
Страница 135: ...66001 00600 202004 V1 2...