Communication extension card
EtherNet/IP communication card
-57-
cable into the port without regard to its direction. Figure 5-1 shows the ports, and Table 5-1
describes the port pins.
Figure 5-1 Two standard RJ45 ports
Table 5-1 Standard RJ45 port pins
Pin
Name
Description
1
TX+
Transmit Data+
2
TX-
Transmit Data-
3
RX+
Receive Data+
4
n/c
Not connected
5
n/c
Not connected
6
RX-
Receive Data-
7
n/c
Not connected
8
n/c
Not connected
4. State indicators
The EtherNet/IP communication card provides four LED indicators and four net port indicators
to indicate its states. Table 5-2 describes the state indicators.
Table 5-2 State indicators
LED
Color
State
Description
LED1
Green
On
The card is shaking hands with the VFD.
Blinking (1Hz)
The card and VFD communicate normally.
Off
The card and VFD communicate improperly.
LED2
Green
On
The communication between the card and PLC
is online and data interchange is allowed.
Blinking (1Hz)
IP address conflict between the card and PLC.
Off
The communication between the card and PLC
is offline.
LED3
Red
On
Failed to set up I/O between the card and PLC.
Blinking (1Hz)
Incorrect PLC configuration.
Blinking (2Hz)
The card failed to send data to the PLC.
Blinking (4Hz)
The connection between the card and PLC
timed out.
Off
No fault.
LED4
Red
On
3.3V power indicator.