Communication extension card
PROFINET communication card
-53-
Function
code
Word
Value range
Default
value
P16.53
Transmitted PZD12
9: Linear speed of the running (×1, m/s)
10: Ramp frequency reference
11: Fault code
12: AI1 value (×100, V)
13: AI2 value (×100, V)
14: AI3 value (×100, V)
15: HDIA frequency (×100, kHz)
16: Terminal input state
17: Terminal output state
18: PID reference (×100, %)
19: PID feedback (×100, %)
20: Rated torque of the motor
21: MSB of position reference (signed
number)
22: LSB of position reference (unsigned
number)
23: MSB of position feedback (signed
number)
24: LSB of position feedback (unsigned
number)
25: State word
26: HDIB frequency value (×100, kHz)
0
PKW zone
PKW zone (parameter identification flag PKW1––numerical zone): The PKW zone describes
the processing mode of the parameter identification interface. A PKW interface is not a
physical interface but a mechanism that defines the transmission mode (such reading and
writing a parameter value) of a parameter between two communication ends.
Parameter
identification (PKW)
Process data
PKW1
PKW2
PKW3
PKW4
CW
SW
PZD2
PZD2
Request
No.
Response
No.l
Parameter
address
Parameter
value error
No.
Parameter
value
Figure 4-5 Parameter identification zone
In the periodic communication, the PKW zone consists of four 16-bit words. The following
table describes the definition of each word.