Communication extension card
Related function codes
-119-
Function
code
Name
Parameter description
Setting
range
Default
value
LED tens place: Switching in running
0: Disabled
1: Enabled
P09.00
PID reference
source
0: Keypad (P09.01)
1–6: Reserved
7:
PROFIBUS/CANopen/DeviceNet
communication
8: Ethernet communication
9: Reserved
10: EtherCAT/PROFINET/EtherNetIP
communication
11–12: Reserved
0–12
0
P09.02
PID feedback
source
0: AI1
1–4: Reserved
5:
PROFIBUS/CANopen/DeviceNet
communication
6: Ethernet communication
7: Reserved
8:
EtherCAT/PROFINET/EtherNetIP
communication
9–10: Reserved
0–10
0
P15.01
Module address 0–127
0–127
2
P15.02
Received PZD2 0: Invalid
1: Set frequency (0–Fmax, unit: 0.01
Hz)
2: PID reference (0–1000, in which
1000 corresponds to 100.0%)
3: PID feedback (0–1000, in which 1000
corresponds to 100.0%)
4: Torque setting (-3000–+3000, in
which 1000 corresponds to 100.0% of
the rated current of the motor)
5: Setting of the upper limit of forward
running frequency (0–Fmax, unit: 0.01
Hz)
6: Setting of the upper limit of reverse
running frequency (0–Fmax, unit: 0.01
Hz)
0–31
0
P15.03
Received PZD3
0–31
0
P15.04
Received PZD4
0–31
0
P15.05
Received PZD5
0–31
0
P15.06
Received PZD6
0–31
0
P15.07
Received PZD7
0–31
0
P15.08
Received PZD8
0–31
0
P15.09
Received PZD9
0–31
0
P15.10
Received PZD10
0–31
0
P15.11
Received PZD11
0–31
0
P15.12
Received PZD12
0–31
0