Communication extension card
PROFINET communication card
-50-
analog and digital input terminals, VFD control panel, and communication modules (such as
RS485 and CH-PA01 adapter modules). To enable the control over VFD devices through
PROFINET, you need to set the communication module as the controller of the VFD device.
Actual value: An actual value is a 16-bit word that includes information about VFD device
operation. The monitoring function is defined through VFD parameters. The conversion scale
of an integer transmitted as an actual value from the VFD device to the master depends on the
set function. For more description, see the related VFD operation manual.
Note:
A VFD device always checks the bytes of a CW and reference value.
Task packet (master station -> VFD)
CW: The first word in a PZD task packet is a VFD CW. Table 4-5 describes Goodrive350
series VFD CWs.
Table 4-5 Goodrive350 series VFD CWs
Bit
Name
Value
Description
0–7
Communication-based
control command
1
Forward running
2
Reverse running
3
Forward jogging
4
Reverse jogging
5
Stop
6
Coast to stop (emergency stop)
7
Fault reset
8
Stop jogging
8
Enable writing
1
Enable writing (mainly through PKW1 to PKW4)
9–10
Motor group setting
00
Motor 1
01
Motor 2
11
Control mode
switching
1
Enable torque/speed control switching
0
Disable switching
12
Reset power
consumption to zero
1
Enable
0
Disable
13
Pre-excitation
1
Enable
0
Disable
14
DC braking
1
Enable
0
Disable
15
Heartbeat reference
1
Enable
0
Disable
Reference value (REF): The second to twelfth words in a PZD task packet are the main
settings. The main frequency settings are provided by the main setting signal source. Table
4-6 describes the settings of Goodrive350 series VFD.