Communication extension card
PROFINET communication card
-52-
series VFD SWs.
Table 4-7 Goodrive350 series VFD SWs
Bit
Name
Value
Description
0–7
Running state
1
In forward running
2
In reverse running
3
Stopped
4
Faulty
5
POFF
8
Bus voltage established
1
Ready to run
0
Not ready to run
9–10
Motor group feedback
0
Motor 1
1
Motor 2
11
Motor type feedback
1
Synchronous motor
0
Asynchronous motor
12
Overload pre-alarm feedback
1
Overload pre-alarm generated
0
No overload pre-alarm generated
13–14
Run/Stop mode
0
Keypad-based control
1
Terminal-based control
2
Communication-based control
3
Reserved
15
Heartbeat feedback
1
Heartbeat feedback
0
No heartbeat feedback
Actual value (ACT): The second to twelfth words in a PZD task packet are the main actual
values. The main actual frequency values are provided by the main actual value signal source.
Table 4-8 Actual state values of Goodrive350 series VFD
Function
code
Word
Value range
Default
value
P16.43
Transmitted PZD2 0: Invalid
1: Running frequency (×100, Hz)
2: Set frequency (×100, Hz)
3: Bus voltage (×10, V)
4: Output voltage (×1, V)
5: Output current (×10, A)
6: Actual output torque (×10, %)
7: Actual output power (×10, %)
8: Rotating speed of the running (×1,
RPM)
0
P16.44
Transmitted PZD3
0
P16.45
Transmitted PZD4
0
P16.46
Transmitted PZD5
0
P16.47
Transmitted PZD6
0
P16.48
Transmitted PZD7
0
P16.49
Transmitted PZD8
0
P16.50
Transmitted PZD9
0
P16.51
Transmitted PZD10
0
P16.52
Transmitted PZD11
0