Communication extension card
PROFIBUS communication card
-2-
Chapter 2 PROFIBUS communication card
2.1 Overview
PROFIBUS communication cards are optional accessories for VFDs. They can be used to
connect VFDs to PROFIBUS networks. On a PROFIBUS network, VFDs are slave devices.
The following functions can be performed by using a PROFIBUS communication card:
•
Transmit control commands (such as start, stop, and fault reset) to a VFD.
•
Transmit speed or torque reference signals to a VFD.
•
Obtain state values and actual values from a VFD.
•
Modify parameter values of a VFD.
2.2 Features
1. PROFIBUS is an international open fieldbus standard that can implement data exchange
between various automation components. It is widely applicable to automation in various
industries, such as the manufacturing, process, building, transportation, and power
industries. It provides effective solutions for implementing integrated automation and
intelligentization of field devices.
2. PROFIBUS
consists
of
three
mutually
compatible
components,
namely
PROFIBUS-Decentralised Peripherals (DP), PROFIBUS-Process Automation (PA), and
PROFIBUS-Fieldbus Message Specification (FMS). It adopts the master-slave mode and
is generally used for periodic data exchange between VFD devices. PRNV
PROFIBUS-DP adapter modules support only the PROFIBUS-DP protocol.
3. The transmission media of a PROFIBUS field bus are twisted pairs (complying with the
RS-485 standard), paired cables, or optical cables. The baud rate ranges from 9.6 kbit/s
to 12 Mbit/s. The maximum length of a fieldbus cable must be within the range of 100 m
to 1200 m, and the specific length depends on the selected transmission rate (see the
chapter of "Technical Data" in the VFD manual). A maximum of 31 nodes can be
connected to one PROFIBUS network segment when no repeater is used. If repeaters
are used, a maximum of 127 nodes (including the repeaters and master stations) can be
connected.
4. In PROFIBUS communication, tokens are transmitted between master stations or by
master stations to slave stations. Single-master or multi-master systems are supported.
The node to respond to the command of a master is selected by the master station,
generally a programmable logic controller (PLC). For cyclic master-slave user data
transmission and non-cyclic master-master data transmission, a master can also transmit
commands to multiple nodes in broadcast mode. When the broadcast mode is adopted,
the nodes do not need to transmit feedback signals to the master. On PROFIBUS
networks, nodes cannot communicate with each other.