Goodrive300-16 special inverter for HVAC
Appendix A
101
Function
code
Name
Detailed instruction of parameters
Default
value
Modify
14: Bacnet read input function parameter
15: Bacnet write input function parameter
16: Bacnet write input function code
17: PID1 reference source 2, range(0~1000,1000
corresponds to 100.0%)
18: PID1 feedback source 2, range(0~1000,1000
corresponds to 100.0%)
19: PID2 reference source 1, range(0~1000,1000
corresponds to 100.0%)
20: PID2 feedback source 1, range(0~1000,1000
corresponds to 100.0%)
21: Water level of inlet sump, range(0~1000,1000
corresponds to 100.0%)
P15.13
PZD2
sending
0: Invalid
1: Running frequency(*100,Hz)
2: Setting frequency(*100,Hz)
3: Bus voltage(*10,V)
4: Output voltage(*1,V)
5: Output current (*10,A)
6: Output torque actual value(*10,%)
7: Output power actual value(*10,%)
8: Running rotating speed(*1,RPM)
9: Running linear speed (*1,m/s)
10: Ramp given frequency
11: Fault code
12: AI1 value (*100,V)
13: AI2 value (*100,V)
14: AI3 value (*100,V)
15: PULSE frequency value (*100,kHz)
16: Terminals input state
17: Terminals output state
18: PID1 reference(*100,%)
19: PID1 feedback(*100,%)
20: Motor rated torque
0
○
P15.14
PZD3
sending
0
○
P15.15
PZD4
sending
0
○
P15.16
PZD5
sending
0
○
P15.17
PZD6
sending
0
○
P15.18
PZD7
sending
0
○
P15.19
PZD8
sending
0
○
P15.20
PZD9
sending
0
○
P15.21
PZD10
sending
0
○
P15.22
PZD11
sending
0
○
P15.23
PZD12
0
○