![INVT GD300-16 Скачать руководство пользователя страница 94](http://html1.mh-extra.com/html/invt/gd300-16/gd300-16_operation-manual_2085742094.webp)
Goodrive300-16 special inverter for HVAC
Appendix A
93
Function
code
Name
Detailed instruction of parameters
Default
value
Modify
0: Output phase loss protection disable
1: Output phase loss protection enable
LED hundreds:
0: Hardware input phase loss protection disable
1: Hardware input phase loss protection enable
P11.01
Frequency-
decreasing
at sudden
power loss
0: Disable
1: Enable
0
○
P11.02
Frequency
decreasing
ratio at
sudden
power loss
0.00Hz/s~P00.03 (Max.output frequency)
10.00
Hz/s
○
P11.03
Overvoltage
stall
protection
0: Disable
1: Enable
1
○
P11.04
Voltage
protection
of
overvoltage
stall
120~150% (standard bus voltage)(380V)
136%
○
120~150% (standard bus voltage)(220V)
120%
P11.05
Current
limit action
selection
0x00~0x11
LED ones: current limit:
0: Invalid
1: Valid
LED tens: overload alarm of hardware current limit
0: Valid
1: Invalid
01
◎