Goodrive300-16 special inverter for HVAC
Appendix A
78
Function
code
Name
Detailed instruction of parameters
Default
value
Modify
P08.06
Jogging
frequency
0.00Hz~P00.03 (Max.output frequency)
5.00Hz
○
P08.07
Jogging
ACC time
0.0~3600.0s
Depend
on
model
○
P08.08
Jogging
DEC time
0.0~3600.0s
Depend
on
model
○
P08.09
Jumping
frequency 1
0.00Hz~P00.03 (Max.output frequency)
0.00Hz
○
P08.10
Jumping
frequency
range 1
0.00Hz~P00.03 (Max.output frequency)
0.00Hz
○
P08.11
Jumping
frequency 2
0.00Hz~P00.03 (Max.output frequency)
0.00Hz
○
P08.12
Jumping
frequency
range 2
0.00Hz~P00.03 (Max.output frequency)
0.00Hz
○
P08.13
Jumping
frequency 3
0.00Hz~P00.03 (Max.output frequency)
0.00Hz
○
P08.14
Jumping
frequency
range 3
0.00Hz~P00.03 (Max.output frequency)
0.00Hz
○
P08.15
Traverse
range
0.0~100.0% (relative to the set frequency)
0.0%
○
P08.16
Sudden
jumping
frequency
range
0.0~50.0% (relative to the traverse range)
0.0%
○
P08.17
Traverse
boost time
0.1~3600.0s
5.0s
○
Содержание GD300-16
Страница 1: ...Goodrive300 16 Special Inverter for HVAC GD300 16 011G 015P 4...