Goodrive300-16 special inverter for HVAC
Appendix A
113
Function
code
Name
Detailed instruction of parameters
Default
value
Modify
P19.08
PID2
feedback
source
0: AI1
1: AI2
2: AI3
3: HDI
4: MODBUS
5: Profibus-DP/CANopen/BACnet/Devicenet
6: Ethernet
7: Reserved
0
○
P19.09
PID2
feedback
filter time
0.000~60.000s
0.000s
○
P19.10
PID output
feature
0~1
0
○
P19.11
Proportiona
l gain
0.00~100.00
1.00
○
P19.12
Integral
time
0.00~30.00s
0.10s
○
P19.13
Differential
time
0.00~10.00s
0.00s
○
P19.14
Sampling
cycle
0.001~10.000s
0.100s
○
P19.15
PID2
control
dead area
0.0~100.0%
1.0%
○
P19.16
Dead area
delay
0.0~300.0s
1.0s
○
P19.17
PID2 output
upper limit
P19.18~100.0%
100.0%
○
P19.18
PID2 output
lower limit
-100.0~P19.17
0.0%
○
P19.19
PID2
deviation
input limit
0.0~100.0%
100.0%
○