Goodrive300-16 special inverter for HVAC
Commissioning guidelines
30
Checking
Item
Method
Criterion
does not mean
that there is
something wrong
with the features.
The
lead
of the
conductors
Ensure that there is no
distortion or color-changing
of the conductors caused by
overheating.
Visual examination
NA
Ensure that there are no
crackles or color-changing of
the protective layers.
Visual examination
NA
Terminals
seat
Ensure that there is no
damage
Visual examination
NA
Filter
capacitors
Ensure that there is no
weeping, color-changing,
crackles and casing
expansion.
Visual examination
NA
Ensure the safety valve is in
the right place.
Estimate the usage
time according to the
maintenance or
measure the static
capacity.
NA
If necessary, measure the
static capacity.
Measure the
capacity by
instruments.
The static capacity
is above or equal
to the original
value *0.85.
Resistors
Ensure whether there is
displacement caused by
overheating.
Smelling and visual
examination
NA
Ensure that there is no
offline.
Visual examination
or remove one
ending to coagulate
The resistors are
in ±10% of the
standard value.