Goodrive300-16 special inverter for HVAC
Commissioning guidelines
19
Function
code
Name
Set
value
Remark
P22.20
Running frequency
when adding motor
50.00Hz
Adjustable according to the actual
situations
P22.21
Delay time when
adding motor
10.0s
Adjustable according to the actual
situations
P22.24
Pressure allowance
when reducing motor
4.0%
Adjustable according to the actual
situations
P22.25
Running frequency
when reducing motor
25.00Hz
Adjustable according to the actual
situations
P22.26
Delay time when
reducing motor
5.0s
Adjustable according to the actual
situations
P22.27
Action of variable
frequency motor
when reducing motor
0
Adjustable according to the actual
situations
P22.28
ACC time of variable
frequency motor
when reducing motor
10.0s
Adjustable according to the actual
situations
P22.29
Multi-motor pressure
loss compensation
0
Adjustable according to the actual
situations
P22.30
Pressure reference
boost value of 1
auxiliary motor
5.0%
Adjustable according to the actual
situations
P22.31
Pressure reference
boost value of 2
auxiliary motors
10.0%
Adjustable according to the actual
situations
P22.32
Pressure reference
boost value of 3
auxiliary motors
15.0%
Adjustable according to the actual
situations
P22.33
Circulation cycle of
power frequency
motor
24.0h
Adjustable according to the actual
situations