Goodrive300-16 special inverter for HVAC
Appendix A
116
Function
code
Name
Detailed instruction of parameters
Default
value
Modify
when
inverter
stops
P20.08
Second
when
inverter
stops
00~59s
00s
○
P20.09
Clock fault
0: Disabled
1: Enabled
0
○
P20.10
Current
second
00~59s
00s
●
P21 Group Fire override function
P21.00
Fire mode
0: Invalid
1: Fire mode 1
2: Fire mode 2
P21.00=0, the fire mode is invalid. The inverter
runs in normal mode and stops at fault. When
P21.00 is non-zero and the fire signal is enabled,
the fire mode will be valid. The inverter will run in
the frequency P21.01.
Fire mode 1, the inverter will keep running unless it
is damaged;
Fire mode 2, the inverter will keep running except
OUT1, OUT2, OUT3, OC1, OC2, OC3, OV1, OV2,
OV3 and SPO faults
0
◎
P21.01
Running
frequency
in fire mode
0.00Hz~P00.03 (Max. output frequency)
50.00Hz
○
P21.02
Fire mode
flag bit
0~1
After the inverter runs in fire mode for 5 minutes,
set the flag bit without warranty handling.
0
●
P21.03
Current
01.01~12.31
00.00
●