Goodrive300-16 special inverter for HVAC
Appendix C
133
The input interference filter can decrease the interference of the inverter to the surrounding
equipments.
Output interference filter can decrease the radio noise cause by the cables between the
inverter and the motor and the leakage current of the conducting wires.
Our company configured some filters for the convenience of the users.
C.3.1 Filter type instruction
Character
designation
Detailed instruction
A
FLT: inverter filter series
B
Filter type
P: power supply filter
L: output filter
C
Voltage degree
04: AC 3PH 380V (-15%)~440V(+10%)
06: AC 3PH 520V (-15%)~690V(+10%)
D
3 bit rated current code,
“015” means 15A
E
Installation type
L: Common type
H: High performance type
F
Utilization environment of the filters
A: the first environment (IEC61800-3:2004) category C1 (EN
61800-3:2004)
B: the first environment (IEC61800-3:2004) category C2 (EN
61800-3:2004)
C: the second environment (IEC61800-3:2004) category C3 (EN
61800-3:2004)
C.3.2 Filter selection
Model
Input filter
Output filter
GD300-16-004G/5R5P-4
FLT-P04016L-B
FLT-L04016L-B
GD300-16-5R5G/7R5P-4
Содержание GD300-16
Страница 1: ...Goodrive300 16 Special Inverter for HVAC GD300 16 011G 015P 4...