Goodrive300-16 special inverter for HVAC
Commissioning guidelines
17
Function
code
Name
Set
value
Remark
PID1 reference
situations
P09.10
PID1 feedback
source 1
1
Adjustable according to the actual
situations
P09.16
Output feature
0
Adjustable according to the actual
situations
P09.17
Proportional gain
1.00
Adjustable according to the actual
situations
P09.18
Integral time
0.10
Adjustable according to the actual
situations
P09.19
Differential time
0.00
Adjustable according to the actual
situations
P22.00
HVAC function
1
HVAC function enabled
P22.01
Hibernation type
1
Hibernate according to the running
frequency
P22.02
Hibernation starting
frequency
40.00Hz
Allow hibernation only when the running
frequency is smaller than the value and
the hold time is larger than P22.04.
P22.03
Hibernation starting
deviation
5.0%
Relative to the maximum PID1 value
Allow hibernation only when the output
feature is positive, feedback is larger than
reference, the absolute value of the actual
deviation is larger than the value and the
hold time is larger than P22.04.
Allow hibernation only when the output
feature is negative, feedback is smaller
than reference, the absolute value of the
actual deviation is larger than the value
and the hold time is larger than P22.04.
P22.04
Hibernation entry
delay time
60.0s
P22.05
PID1 reference
boost
10.0%
Relative to PID1 reference
P22.06
Max. boost time
10.000s
Used to avoid the case where the inverter