Goodrive300-16 special inverter for HVAC
Appendix A
86
Function
code
Name
Detailed instruction of parameters
Default
value
Modify
4: MODBUS
5: Profibus-DP/CANopen/BACnet
6: Ethernet
7: Reserved
P09.12
PID1
feedback
filter time
0.000~60.000s
0.000s
○
P09.13
Feedback
source 1
conversion
gain
0.00~600.00
1.00
○
P09.14
Feedback
source 2
conversion
gain
0.00~600.00
1.00
○
P09.15
Feedback
function
0: No combination feedback source 1
1: Sum feedback source 1+feedback source 2
2: Difference feedback source 1-feedback source 2
3: Average average feedback source 1 and
feedback source 2
4: Minimize minimize feedback source 1 and
feedback source 2
5: Maximize maximize feedback source 1 and
feedback source 2
6: Multi-reference minimum positive deviation and
maximum negative deviation
Calculate the difference of reference source 1 and
feedback source 1, reference source 2 and
feedback source 2 and consider the case when the
feedback is larger than the reference in priority.
If the feedback is larger than the corresponding
reference, take the maximum negative deviation as
PID reference and feedback. If the feedback is
smaller than the corresponding reference, take the
0
○