Goodrive300-16 special inverter for HVAC
Commissioning guidelines
18
Function
code
Name
Set
value
Remark
runs continuously when the running
frequency reaches the upper limit while
the feedback cannot reach the set value
after boost, the inverter will enter
hibernation immediately after boost time.
P22.07
Hibernation waking
frequency
20.00Hz
PID output directly starts superposition
from the frequency when waking up in
close loop.
P22.08
Hibernation waking
deviation
2.0%
Relative to the maximum PID1 value
Allow waking up only when the output
feature is positive, feedback is smaller
than reference, the absolute value of the
actual deviation is larger than the value
and the hold time is larger than P22.09.
Allow waking up only when the output
feature is negative, feedback is larger
than reference, the absolute value of the
actual deviation is larger than the value
and the hold time is larger than P22.09.
P22.09
Hibernation waking
delay time
2.0s
Min. hibernation time
P22.10
Variable frequency
motor operation
0
Set to the fixed variable frequency motor,
invalid when A~H motors are set to
variable frequency motor, set to power
frequency motors when using multiple
motors
P22.11
A motor type
2
Power frequency motor
P22.12
B motor type
2
Power frequency motor
P22.13
C motor type
2
Power frequency motor
P22.19
Pressure allowance
when adding motor
4.0%
Adjustable according to the actual
situations