P05.46
Upper limit
of AI3
P05.44~10.00V
10.00V
○
P05.47
Correspond
ing setting
of
the upper
limit of AI3
-100.0%~100.0%
100.0%
○
P05.48
AI3 input
filter time
0.000s~10.000s
0.100s
○
P05.49
HDI
high-speed
pulse input
function
selection
0: Frequency setting input
1:Counter input
0
◎
P05.50
Lower limit
frequency
of HDI
0.000kHz~P05.52
0.000
kHz
○
P05.51
Correspond
ing setting
of HDI low
frequency
setting
-100.0%~100.0%
0.0%
○
P05.52
Upper limit
frequency
of HDI
P05.50~50.000kHz
50.000
kHz
○
P05.53
Correspond
ing setting
of upper
limit
frequency
of HDI
-100.0%~100.0%
100.0%
○