Goodrive300-16 special inverter for HVAC
Appendix A
49
Function
code
Name
Detailed instruction of parameters
Default
value
Modify
setting for
upper
frequency
of forward
rotation
P03.17
Keypad
setting for
upper
frequency
of reverse
rotation
0.00Hz~P00.03
50.00Hz
○
P03.18
Upper
electromoti
on torque
source
0: Keypad setting upper-limit frequency
1: AI1
2: AI2
3: AI3
4: HDI
5: MODBUS communication
6: Profibus/CANopen/BACnet/Devicenet
communication
7: Ethernet communication
8: Reserved
0
○
P03.19
Upper
braking
torque
source
0
○
P03.20
Keypad
setting of
electromoti
on
torque
0.0~300.0% (motor rated current)
180.0%
○
P03.21
Keypad
setting of
braking
torque
0.0~300.0% (motor rated current)
180.0%
○
P03.22 Weakening 0.1~2.0
0.3
○