![INVT GD300-16 Скачать руководство пользователя страница 26](http://html1.mh-extra.com/html/invt/gd300-16/gd300-16_operation-manual_2085742026.webp)
Goodrive300-16 special inverter for HVAC
Commissioning guidelines
25
Function
code
Name
Set
value
Remark
actual deviation is larger than the value
and the hold time is larger than P22.09.
P22.09
Hibernation waking
delay time
2.0s
Min. hibernation time
P22.10
Variable frequency
motor operation
1
Circulation variable frequency motor
P22.11
A motor type
1
Variable frequency motor
P22.12
B motor type
1
Variable frequency motor
P22.13
C motor type
1
Variable frequency motor
P22.14
D motor type
2
Power frequency motor
P22.15
E motor type
2
Power frequency motor
P22.19
Pressure allowance
when adding motor
4.0%
Adjustable according to the actual
situations
P22.20
Running frequency
when adding motor
50.00Hz
Adjustable according to the actual
situations
P22.21
Delay time when
adding motor
10.0s
Adjustable according to the actual
situations
P22.22
Switch frequency
when adding
variable frequency
motor
50.00Hz
Adjustable according to the actual
situations
P22.23
DEC time of variable
frequency motor
when adding power
frequency motor
10.0s
Adjustable according to the actual
situations
P22.24
Pressure allowance
when reducing motor
4.0%
Adjustable according to the actual
situations
P22.25
Running frequency
when reducing motor
25.00Hz
Adjustable according to the actual
situations
P22.26
Delay time when
reducing motor
5.0s
Adjustable according to the actual
situations
Содержание GD300-16
Страница 1: ...Goodrive300 16 Special Inverter for HVAC GD300 16 011G 015P 4...
Страница 136: ...201610 V2 0 66001 00347 I I...