Goodrive300-16 special inverter for HVAC
Appendix A
123
Function
code
Name
Detailed instruction of parameters
Default
value
Modify
4: AI3
5: MODBUS communication
6: Profibus/CANopen/BACnet/Devicenet
communication
P22.40
Upper limit
of water
level of inlet
sump
0.0~100.0%
60.0%
○
P22.41
Lower limit
of water
level of inlet
sump
0.0~P22.40
40.0%
○
P22.42
Water
shortage
level of inlet
sump
0.0~P22.41
20.0%
○
P22.43
Abnormal
standby
pressure
0.0~100.0% (relative to Max. PID1)
0.0%
○
P22.44
Low PID1
feedback
protection
0.0~100.0% (relative to Max. PID1)
10.0%
○
P22.45
Low PID1
feedback
delay time
0.0~3600.0s
The keypad will display -LP- when PID1 feedback
is smaller than P22.44 and the hold time is larger
than P22.45.
500.0s
○
P22.46
High PID1
feedback
protection
0.0~100.0% (relative to Max. PID1)
80.0%
○
P22.47
High PID1
feedback
delay time
0.0~3600.0s
The keypad will display -HP- when PID1 feedback
is larger than P22.46 and the hold time is larger
500.0s
○