Self-test 

Detector is continuously checking all vital parts responsible for 
proper detection of glass break signal using internal self-test 
procedure.  

Anti-masking  

To test the anti-masking system, follow these steps: 

1.  Put the power on. Seal microphone completely with elastic 

material like plasticine, chewing gum or isolation tape. 

INTRUSION and FAULT relays will open after max. of 
180 s signalling masking of microphone. 

2.  Remove sealing material from microphone. Relays will 

close in less than minute. 

Understanding the LED when the detector 
is in operation 

The LED can have the following states in operation: 

• 

Flashes 1 to 3 times when powered ON: Indication of 
range setting after power-on 

• 

Off: Normal state, no alarms 

• 

Permanently on: Intrusion detected 

– if detector in Latch 

mode 

• 

Permanently on with 1 dip per 3 s: Masking detected 

• 

Permanently on with 2 dips per 3 s: Low supply voltage or 
self-test failure 

• 

Short blink: Antimasking warning 

– foreign object in close 

proximity of microphone 

Understanding the LED when testing the 
detector with GS960-TR tester 

The LED can have the following states during the test: 

 

Flickers: In test mode 

 

Flickers and blinks: In calibration mode 

 

Flashes 1.5 s: Confirms received signal 

• 

Blinks slowly 1 time each 2.5 s after calibration: Set range 
setting to Zone 1 (4 to 9 m) 

• 

Blinks slowly 2 times each 2.5 s after calibration: Set 
range setting to Zone 2 (2 to 4 m) 

• 

Blinks slowly 3 times each 2.5 s after calibration: Set 
range setting to Zone 3 (1 to 2 m) 

Troubleshooting 

Detector does not respond: 

• 

Check the supply voltage and polarity 

LED permanently on: 

• 

Switch off the detector for a short period 

• 

Check if LED is in latching mode (DIP 1 ON) 

LED permanently on with 1 dip per 3 s: 

• 

Check if microphone not masked with foreign material 

LED permanently on with 2 dips per 3 s: 

• 

Check supply voltage 

– it should be higher than 7 V 

No alarm: 

• 

Check the INTRUSION and FAULT relay wiring 

• 

Check the alarm loop wiring 

Specifications 

Type (thickness) of protected glass: 

 

 

Minimum 

Float (4 mm) 

 

Maximum 

Laminated P4 (4 + 4 mm) 

Size of protected glass 

40 × 40 cm min. 

Max range 

9 m 

radius/165° 

Range setting 

Zone 1: 4 to 9 m 
Zone 2: 2 to 4 m 
Zone 3: 1 to 2 m 

Supply voltage 

7 to 30 V DC 

Max. voltage ripple 

2 Vp-p at 12 V, 4 Vp-p at 24 V 

Voltage monitoring 

Fault signalled at < 7 V  

Current consumption, max. 

11.4 mA at 12 V, 7.2 mA 
at 24 V 

D/N signal levels 

DAY: D/N open or < 2.5 V, 
NIGHT: D/N > 2.5 V 

INTRUSION output, FAULT output 

Relay 

INTRUSION and FAULT relay 
contact rating 

50 mA, 50 V DC / peak AC, 
Rs 

≤ 30 Ω 

TAMPER contact rating 

50 mA / 50 V DC / peak AC 

Intrusion/fault indication 

LED 

Environmental class EN 50130-
5:2011, VdS 2110 

Class I 

Operating temp. range 

+5 to 40

°C 

Operating humidity range 

Max. 93% RH 

Housing material 

Plastic ABS, white 

Dimensions (W x H x D) 

68 x 109 x 40 mm 

Security grade 

EN 50131-2-7-1:2012/A1:2013, 
Grade 3; VdS 2332, class B 

Approvals  

VdS: G118505 

Accessory 

GS960-RB plug-in EOL resistor 
board 

Regulatory information 

Manufacturer 

PLACED ON THE MARKET BY: 
UTC Fire & Security Americas Corporation, Inc. 
3211 Progress Drive, Lincolnton, NC, 28092, 
USA 

AUTHORIZED EU REPRESENTATIVE: 
UTC Fire & Security B.V. 
Kelvinstraat 7, 6003 DH Weert, Netherlands 

Содержание GS960AM

Страница 1: ...poration Inc 1 40 P N 422 6368 ML REV F ISS 05FEB19 GS960AM Acoustic Glass Break Detector with Antimasking Installation Sheet EN DE ES FR IT NL PL PT SV 1 2 3 4 5 6 7 1 4 5 6 2 3 1 2 3 1 2 3 4 5 6 7 6...

Страница 2: ...e base Connection to a 24 hour loop The detector is constructed for continuous supervision and is extra resistant to different acoustic disturbances It will function well in most environments However...

Страница 3: ...o the room Table 1 Terminal pins Pin Marking Function 1 Ground 2 Plus 7 to 30 V DC 3 D N Day and Night control of LED 4 INTRUSION INTRUSION relay output C Pin Marking Function 5 INTRUSION INTRUSION re...

Страница 4: ...een LED will light 2 Hold the tester 1 to 3 m from the detector and aim the speaker at it 3 Press the START button once more to initiate the DRC mode The LED on the detector will start to flicker See...

Страница 5: ...nge setting to Zone 3 1 to 2 m Troubleshooting Detector does not respond Check the supply voltage and polarity LED permanently on Switch off the detector for a short period Check if LED is in latching...

Страница 6: ...er GS960AM ist mit einer aktiven Abdeck berwachungs funktion ausgestattet die bei einer Abdeckung des Mikrofons des Melders mittels eines Relais eine Meldung generiert Der GS960AM ist nach EN 50131 2...

Страница 7: ...r mit dem Bleistift an der Wand 4 F r die beigef gten gewindeselbstschneidenden Schrauben benutzen Sie einen 2 5 mm dicken Bohrer Wenn n tig wenden Sie Wandd bel an 5 Bei Bedarf brechen Sie die vorges...

Страница 8: ...Art auf der Innenseite des Fensters Reichweite 1 2 m 2 4 m 4 9 m Einfach u Mehrfach verglasung Verbundsicherheitsglas VSG Zone 1 Anbringung des Melderdeckels 1 Setzen Sie Krallen des Geh use Deckels i...

Страница 9: ...on ist bei beiden Ger ten sowohl beim Melder als auch bei dem Testger t zeitbegrenzt Wenn keine weiteren Tests durchgef hrt werden wird die DRC Funktion des Melders sowie des Testers GS960 TR nach 3 4...

Страница 10: ...109 x 40 mm Sicherungsklasse EN 50131 2 7 1 2012 A1 2013 Grad 2 VdS 2332 Klasse B Zertifizierung VdS G118505 Zubeh r GS960 RB einsteckbare EOL Widerstandsplatine Rechtliche Hinweise Hersteller INVERKE...

Страница 11: ...detector durante 3 y 4 semanas antes de decidir utilizarlo sin interrupciones En casos poco frecuentes una combinaci n de sonidos aleatorios puede activar una alarma Eventos se alizados El detector t...

Страница 12: ...GS960AM en un sistema Advisor Advanced sin la tener que agregar resistencias EOL Switch DIP Las funciones del switch DIP se describen en la Tabla 2 m s adelante Tabla 2 Funciones del switch DIP DIP F...

Страница 13: ...START una vez m s para iniciar el modo DRC El LED en el detector comenzar a parpadear Consulte la Figura 8 4 Vaya a la distancia m s alejada m x 9 m del cristal que desea proteger y apunte el altavoz...

Страница 14: ...5 s despu s de la calibraci n establezca el ajuste de alcance en Zona 2 de 2 a 4 m Parpadea lentamente 3 veces cada 2 5 s despu s de la calibraci n establezca el ajuste de alcance en Zona 3 de 1 a 2...

Страница 15: ...ation num rique DRC Cela permet au d tecteur de faire la distinction entre un bris de vitre v ritable et d autres sons non pertinents Le d tecteur est con u pour une utilisation en int rieur Sa port e...

Страница 16: ...la base avec des pinces 6 Acheminez y le c blage 7 Connectez les fils aux borniers Consultez le Tableau ci dessous pour obtenir des informations suppl mentaires 8 Utilisez le serre c ble fourni pour f...

Страница 17: ...in de tester et calibrer le d tecteur pour une position optimale Test et calibration Le testeur GS960 TR est un outil sp cialement d velopp pour calibrer et ajuster le d tecteur GS960AM afin d obtenir...

Страница 18: ...e en continu intrusion d tect e si le d tecteur est en mode de verrouillage Allum en continu avec 1 extinction toutes les 3 secondes masquage d tect Allum en continu avec 2 extinctions toutes les 3 s...

Страница 19: ...www utcfssecurityproducts fr mail_support htm IT Istruzioni per l installazione Descrizione Il modello GS960AM un rilevatore acustico di rottura vetro che emette un allarme quando il vetro viene distr...

Страница 20: ...in un raggio di 50 cm dal rilevatore Il rilevatore non deve essere installato vicino a prese d aria o grandi ostacoli che riflettono il suono Non montare mai il rilevatore negli angoli Installazione 1...

Страница 21: ...na 3 Zona 2 Zona 1 Bassi disturbi Zona 1 Triplo vetro Galleggiante e temperato Zona 1 Design della finestra Tipo di vetro all interno della stanza Intervallo 1 2 m 2 4 m 4 9 m Doppio vetro con pellico...

Страница 22: ...n si verifica alcuna attivit entro 3 o 4 minuti Controllo D N giorno notte Il controllo D N consente di controllare a distanza le indicazioni di allarme dei rilevatori e il reset remoto durante la tra...

Страница 23: ...UTC FIRE SECURITY NON PU GARANTIRE CHE LE PERSONE O GLI ENTI CHE ACQUISTANO I SUOI PRODOTTI COMPRESI I RIVENDITORI AUTORIZZATI DISPONGANO DELLA FORMAZIONE O ESPERIENZA ADEGUATE PER ESEGUIRE LA CORRETT...

Страница 24: ...d kantoren zijn tijdens de installatie geen speciale gereedschappen nodig In ruimten met gecompliceerde akoestiek wordt het aanbevolen om de GS960 TR tester te gebruiken De GS960 TR kan ook worden geb...

Страница 25: ...UIT 3 1 tot 2 m Zone 3 AAN AAN Voorgestelde instellingen van de detector afhankelijk van het raamontwerp en het glastype Controleer de raamconstructies en verifieer welk soort glas wordt gebruikt en...

Страница 26: ...ndigen Als het door de detector gemeten DRC bereik afwijkt van de werkelijke DIP switch instellingen blijft de LED 1 tot 3 keer knipperen en wordt het juiste bereiknummer dat in de detector moet worde...

Страница 27: ...N 50130 5 2011 VdS 2110 Klasse I Bedrijfstemperatuurbereik 5 tot 40 C Operationeel vochtigheidsbereik Max 93 RH Materiaal van behuizing Kunststof ABS wit Afmetingen B x H x D 68 x 109 x 40 mm Beveilig...

Страница 28: ...u W rzadkich przypadkach alarm mo e wyzwoli po czenie r nych losowych d wi k w Sygnalizowane zdarzenia Czujka ma dwa przeka niki i jeden mikroprze cznik do sygnalizowania wykrytych i przetworzonych zd...

Страница 29: ...ni ej Tab 2 Funkcje prze cznika DIP DIP Funkcja Ustawienia 1 Tryb przeka nika W AMANIE ZA Zatrzask WY Auto DIP Funkcja Ustawienia 2 Ustawienie zasi gu 4 do 9 m Strefa 1 2 do 4 m Strefa 2 1 do 2 m Stre...

Страница 30: ...rysunek 8 4 Ustaw si mo liwie daleko maks 9 m od szyby kt r chcesz zabezpieczy i skieruj g o nik na czujk Patrz rysunek 9 Zakres DRC obliczony przez czujk zostanie wy wietlony w postaci liczby impuls...

Страница 31: ...czujk na kr tki okres Sprawd czy dioda LED jest w trybie zatrzasku DIP 1 w czony Dioda LED trwale w czona z 1 zga ni ciem raz na 3 sek Sprawd czy mikrofon nie jest zamaskowany cia ami obcymi Dioda LE...

Страница 32: ...no teto ou numa parede com uma linha de vis o livre para a janela a proteger O GS960AM est equipado com uma fun o AM um rel separado que emite um alarme no caso de sabotagem do microfone O GS960AM es...

Страница 33: ...detetor 9 Fixe o detetor firmemente na base com os parafusos fornecidos 10 Defina a faixa desejada ou seja a configura o de sensibilidade do detetor usando o interruptor DIP n 2 e 3 Consulte Interrup...

Страница 34: ...lvida para calibrar e ajustar o detetor GS960AM para uma fun o otimizada na sala ac stica o procedimento DRC Digital Room Compensation Ao testar as configura es do detetor n o necess rio abri lo novam...

Страница 35: ...bjeto estranho nas proximidades do microfone Compreender o LED ao testar o detetor com o aparelho de teste GS960 TR O LED pode ter os seguintes estados durante o teste Cintila No modo de teste Cintila...

Страница 36: ...u SV Installationsanvisning Beskrivning GS960AM r en akustisk glaskross detektor som ger larm n r glas krossas vid ett inbrotts f rs k p t ex f nster d rrar med glas samt glaspartier Detektorn r baser...

Страница 37: ...r montering p v gg eller i tak 2 Lossa frontskruven och avl gsna fronten 3 Anv nd bakstycket som borrmall och markera ut h len med en penna 4 Anv nd en 2 5 mm borr f r medf ljande skruvar eller annan...

Страница 38: ...att 1 till 3 blinkningar 3 Anv nd GS960 TR f r att testa och kalibrera detektorn f r b sta inst llning Se dess handhavandeinstruktion Test och kalibrering GS960 TR r ett testverktyg som tillverkas spe...

Страница 39: ...detektorn r Inst lld f r LATCH med DIP 1 Lyser med 1 dipp var 3 e s Maskering detekterad Lyser med 2 dippar var 3 e s L g sp nning eller sj lvtestfel Kort blink Antimask varning fr mmande objekt n ra...

Страница 40: ...K PER DESS PRODUKTER INKLUSIVE KVALIFICERAD F RS LJARE ELLER TERF RS LJARE R ORDENTLIGT UTBILDAD ELLER HAR ERFARENHET AV ATT INSTALLERA BRAND OCH S KERHETSRELATERADE PRODUKTER F r mer information om...

Отзывы: