You do not have to turn off the server to install or replace hot-swap power
supplies, hot-swap fans, or hot-plug Universal Serial Bus (USB) devices.
However, you must turn off the server before you perform any steps that
involve removing or installing adapter cables and you must disconnect the
power source from the server before you perform any steps that involve
removing or installing a riser card.
v
Blue on a component indicates touch points, where you can grip the component
to remove it from or install it in the server, open or close a latch, and so on.
v
Orange on a component or an orange label on or near a component indicates
that the component can be hot-swapped, which means that if the server and
operating system support hot-swap capability, you can remove or install the
component while the server is running. (Orange can also indicate touch points
on hot-swap components.) See the instructions for removing or installing a
specific hot-swap component for any additional procedures that you might have
to perform before you remove or install the component.
v
When you are finished working on the server, reinstall all safety shields, guards,
labels, and ground wires.
System reliability guidelines:
The system reliability guidelines to ensure proper system cooling.
To help ensure proper system cooling and system reliability, make sure that the
following requirements are met:
v
Each of the drive bays has a drive or a filler panel and electromagnetic
compatibility (EMC) shield installed in it.
v
Each of the power-supply bays has a power supply or a filler installed in it.
v
If the server has redundant power, each of the power-supply bays has a power
supply installed in it.
v
There is adequate space around the server to allow the server cooling system to
work properly. Leave approximately 50 mm (2.0 in.) of open space around the
front and rear of the server. Do not place objects in front of the fans. For proper
cooling and airflow, replace the server cover before you turn on the server.
Operating the server for extended periods of time (more than 30 minutes) with
the server cover removed might damage server components.
v
You have followed the cabling instructions that come with optional adapters.
v
You have replaced a failed fan within 48 hours.
v
You have replaced a hot-swap fan within 30 seconds of removal.
v
You have replaced a hot-swap drive within 2 minutes of removal.
v
You have replaced a failed hot-swap power supply within 2 minutes of removal.
v
You do not operate the server without the air baffle installed. Operating the
server without the air baffle might cause the microprocessor to overheat.
v
Microprocessor socket 2 always contains either a socket cover or a
microprocessor and heat sink.
v
You have installed the fifth and sixth fans when you installed the second
microprocessor option.
284
System x3650 M5 Type 5462: Installation and Service Guide
Содержание System x3650 M5
Страница 1: ...System x3650 M5 Type 5462 Installation and Service Guide ...
Страница 2: ......
Страница 3: ...System x3650 M5 Type 5462 Installation and Service Guide ...
Страница 8: ...vi System x3650 M5 Type 5462 Installation and Service Guide ...
Страница 16: ...xiv System x3650 M5 Type 5462 Installation and Service Guide ...
Страница 58: ...42 System x3650 M5 Type 5462 Installation and Service Guide ...
Страница 86: ...70 System x3650 M5 Type 5462 Installation and Service Guide ...
Страница 320: ...304 System x3650 M5 Type 5462 Installation and Service Guide ...
Страница 832: ...816 System x3650 M5 Type 5462 Installation and Service Guide ...
Страница 988: ...972 System x3650 M5 Type 5462 Installation and Service Guide ...
Страница 992: ...976 System x3650 M5 Type 5462 Installation and Service Guide ...
Страница 1001: ...Taiwan Class A compliance statement Notices 985 ...
Страница 1002: ...986 System x3650 M5 Type 5462 Installation and Service Guide ...
Страница 1008: ...992 System x3650 M5 Type 5462 Installation and Service Guide ...
Страница 1009: ......
Страница 1010: ... Part Number 00AK781 Printed in USA 1P P N 00AK781 ...