v
Follow the suggested actions in the order in which they are listed in the Action column until the problem is
solved.
v
See Chapter 4, “Parts listing, Types 7871 and 1949,” on page 41 to determine which components are CRUs and
which components are FRUs.
v
If an action step is preceded by “(Trained service technician only),” that step must be performed only by a
trained service technician.
Error Code
Type
Error Message
Action
0x80010900
Error
System board (Inlet Temp)
temperature over/under critical
threshold with chassis reading:
X
, Threshold:
Y
1.
Make sure that the room temperature is within
the operating specifications (see “Features and
specifications” on page 8).
2.
Make sure that none of the air vents on the
BladeCenter unit and on the blade server are
blocked.
3.
Make sure that all of the fans on the BladeCenter
unit are running.
0x80010B00
Error
System board (Inlet Temp)
temperature over/under
non-recoverable threshold.
Reading: X, Threshold: Y
1.
Make sure that the room temperature is within
the operating specifications (see “Features and
specifications” on page 8).
2.
Make sure that none of the air vents on the
BladeCenter unit and on the blade server are
blocked.
3.
Make sure that all of the fans on the BladeCenter
unit are running.
0x80070100
Warning
Memory device
X
, temperature
(DIMM
X
Temp) warning [Note:
X
=1-18]
1.
Make sure that the room temperature is within
the operating specifications (see “Features and
specifications” on page 8).
2.
Make sure that none of the air vents on the
BladeCenter unit and on the blade server are
blocked.
3.
Make sure that all of the fans on the BladeCenter
unit are running.
0x80070100
Warning
Processor
X
, temperature (CPU
X
OverTemp) warning [Note:
X
=1-2]
1.
Make sure that the room temperature is within
the operating specifications (see “Features and
specifications” on page 8).
2.
Make sure that none of the air vents on the
BladeCenter unit and on the blade server are
blocked.
3.
Make sure that all of the fans on the BladeCenter
unit are running.
0x80070200
Error
Memory device
X
, temperature
(DIMM
X
Temp) critical [Note:
X
=1-18]
1.
Make sure that the room temperature is within
the operating specifications (see “Features and
specifications” on page 8).
2.
Make sure that none of the air vents on the
BladeCenter unit and on the blade server are
blocked.
3.
Make sure that all of the fans on the BladeCenter
unit are running.
106
BladeCenter HS22V Type 7871 and 1949: Problem Determination and Service Guide
Содержание BladeCenter HS22V 7871
Страница 1: ...BladeCenter HS22V Type 7871 and 1949 Problem Determination and Service Guide...
Страница 2: ......
Страница 3: ...BladeCenter HS22V Type 7871 and 1949 Problem Determination and Service Guide...
Страница 16: ...xiv BladeCenter HS22V Type 7871 and 1949 Problem Determination and Service Guide...
Страница 20: ...4 BladeCenter HS22V Type 7871 and 1949 Problem Determination and Service Guide...
Страница 34: ...18 BladeCenter HS22V Type 7871 and 1949 Problem Determination and Service Guide...
Страница 64: ...48 BladeCenter HS22V Type 7871 and 1949 Problem Determination and Service Guide...
Страница 112: ...96 BladeCenter HS22V Type 7871 and 1949 Problem Determination and Service Guide...
Страница 240: ...224 BladeCenter HS22V Type 7871 and 1949 Problem Determination and Service Guide...
Страница 244: ...228 BladeCenter HS22V Type 7871 and 1949 Problem Determination and Service Guide...
Страница 252: ...236 BladeCenter HS22V Type 7871 and 1949 Problem Determination and Service Guide...
Страница 257: ......
Страница 258: ...Part Number 00Y8038 Printed in USA 1P P N 00Y8038...