iLO user name:________________________
iLO network name:_____________________
iLO password:_________________________
4.
Install the optional PCIe cards, if necessary.
If the optional PCIe cards were ordered with the system, they have been preinstalled. If the cards
were ordered separately, install them now.
1
2
3
4
5
6
Figure 14: PCI slot numbers
a.
Install the network cards starting in PCI slot 1 and then additional network cards in slots 2, 4, and
5 in that order.
b.
Install the FC cards starting at PCI slot 5 and then additional FC cards in slots 4, 2, and 1 in that
order.
c.
Verify that the correct SFP+ transceivers are fitted, if necessary.
For detailed installation instructions, see
5.
Install the server in the rack.
a.
Install the rail kit for the StoreOnce server. See the installation instructions that ship with the rail
kit.
b.
Insert the two locking nuts for the server into the rack; one on each front column.
c.
Install the server into the rack and secure it using the thumbscrews on the front bezel of the
server.
6.
Install the rails for the base storage enclosure in the rack, directly under the server.
a.
Adjust the back bracket on the standard rail kit to accommodate the storage enclosure. Attach
rear hold down brackets by sliding the tab with the arrow pointed forward (1) into the
corresponding slot on the left and right side of the rear of the chassis. Use the black headed
thumb screw to secure tightly to the rail in the second hole from the rear (2).
NOTE:
It is easier to make this adjustment prior to mounting the rails.
40
HPE StoreOnce 5200 System