CHAPTER 4 - INSTALLATION INSTRUCTIONS
4 - 37
Four Wire Isolated Signal Input, Transmitter Connection for Apex
01
Screened
Cable
Arrows Indicate
Direction of Loop
Current Flow
+24V
4 - 20mA (-)
4 - 20mA (+)
0V
Cabinet
Protective Earth
+24V
0V
Apex Transmitter
Note: The Apex transmitter should be earthed locally. The transmitter is earthed through the
Earth Stud, to avoid earth loops the screen sheath of the cable should only be connected
at the transmitter.
28
29
Relay/Field Interface Card
05701-A-0326
05701-A-0327
05701-A-0328
05701-A-0329
05701-A-0330
Single Channel Control Card 4 - 20mA 05701-A-0301
Fitted with 4 - 20mA Sensor Drive 05701-A-0283
Link Positions
LK1
LK12
LK9
LK6
36
NS
35
SK4
(Comms
and
Power)
Apex
1
2
3
4
5
6
7
* The 24V supply for the transmitter
may be obtained from either the
Relay/Field Interface Card terminals
35 (+24V) and 36 (0V), or a separate
field supply.
Apex
Link Settings:
J4
J5
Содержание 5701
Страница 1: ...Sieger System 57 5701 Control System Operating Instructions ...
Страница 45: ...2 32 MAN0443 P65 Issue 13 Aug 04 5701 Control System 05701 M 5001 A02279 CHAPTER 2 SYSTEM DESCRIPTION ...
Страница 63: ...3 18 CHAPTER 3 CONTROLS AND FACILITIES MAN0443 P65 Issue 13 Aug 04 5701 Control System 05701 M 5001 A02279 ...
Страница 139: ...4 76 MAN0443 P65 Issue 13 Aug 04 5701 Control System 05701 M 5001 A02279 CHAPTER 4 INSTALLATION INSTRUCTIONS ...
Страница 173: ...6 12 MAN0443 P65 Issue 13 Aug 04 5701 Control System 05701 M 5001 A02279 CHAPTER 6 OPERATING INSTRUCTIONS ...
Страница 209: ...9 4 MAN0443 P65 Issue 13 Aug 04 5701 Control System 05701 M 5001 A02279 CHAPTER 9 ORDERING INFORMATION ...