4 - 34
MAN0443.P65 Issue 13 Aug 04
5701 Control System
05701-M-5001 A02279
CHAPTER 4 - INSTALLATION INSTRUCTIONS
Opus/Lifeline II Four Wire Isolated Signal, Transmitter Connection for Opus/Lifeline II
01
Screened
Cable
Cabinet
Protective Earth
+24V
0V
Note: Where the sensor is earthed locally, either to the stud or through the sensor casing or
mounting, to avoid earth loops the screen sheath of the cable should only be connected
at one end, i.e. the sensor or at the relay/interface card.
28
29
Relay/Field Interface Card
05701-A-0326
05701-A-0327
05701-A-0328
05701-A-0329
05701-A-0330
Single Channel Control Card 4 - 20mA 05701-A-0301
Fitted with 4 - 20mA Sensor Drive 05701-A-0283
* The 24V supply for the transmitter
may be obtained from either the
Relay/Field Interface Card
terminals 35 (+24V) and 36 (0V), or
a separate field supply.
Link Positions
LK1
LK12
LK9
LK6
36
NS
35
5
1
3
Opus/Lifeline II Transmitter
4 - 20mA (-)
4 - 20mA (+)
6
Screen to
cable gland
J5
J4
Arrows Indicate
Direction of Loop
Current Flow
Содержание 5701
Страница 1: ...Sieger System 57 5701 Control System Operating Instructions ...
Страница 45: ...2 32 MAN0443 P65 Issue 13 Aug 04 5701 Control System 05701 M 5001 A02279 CHAPTER 2 SYSTEM DESCRIPTION ...
Страница 63: ...3 18 CHAPTER 3 CONTROLS AND FACILITIES MAN0443 P65 Issue 13 Aug 04 5701 Control System 05701 M 5001 A02279 ...
Страница 139: ...4 76 MAN0443 P65 Issue 13 Aug 04 5701 Control System 05701 M 5001 A02279 CHAPTER 4 INSTALLATION INSTRUCTIONS ...
Страница 173: ...6 12 MAN0443 P65 Issue 13 Aug 04 5701 Control System 05701 M 5001 A02279 CHAPTER 6 OPERATING INSTRUCTIONS ...
Страница 209: ...9 4 MAN0443 P65 Issue 13 Aug 04 5701 Control System 05701 M 5001 A02279 CHAPTER 9 ORDERING INFORMATION ...