MAN0443.P65 Issue 13 Aug 04
5701 Control System
05701-M-5001 A02279
CHAPTER 4 - INSTALLATION INSTRUCTIONS
4 - 65
15.
REMOTE INPUT CONNECTIONS
CAUTION
Connecting voltages in excess of 32V to the remote inputs may
cause permanent damage to the Single Channel Control Card.
There are two remote inputs, RESET and INHIBIT, which are individually
configurable for active high or active low operating modes. Check the
configuration sheet supplied with the system to determine the factory
configured operating modes. The operating mode can be reconfigured
easily using a computer attached to the Engineering Port. Contact
Zellweger Analytics or your local agent for more information.
The switching level of the remote input pins (when enabled) is
approxi2V with respect to the dc system 0V. The inputs
require less than 5mA drive current and irrespective of configuration
are internally pulled down to system 0V.
Active high remote inputs may be left unconnected or can be connected
to +24V via a normally open contact. The remote input will operate
whenever the contact closes.
Active low remote inputs may be connected to +24V via a normally
closed contact. The remote input will operate whenever the contact
opens.
Do not leave active low inputs unconnected.
Содержание 5701
Страница 1: ...Sieger System 57 5701 Control System Operating Instructions ...
Страница 45: ...2 32 MAN0443 P65 Issue 13 Aug 04 5701 Control System 05701 M 5001 A02279 CHAPTER 2 SYSTEM DESCRIPTION ...
Страница 63: ...3 18 CHAPTER 3 CONTROLS AND FACILITIES MAN0443 P65 Issue 13 Aug 04 5701 Control System 05701 M 5001 A02279 ...
Страница 139: ...4 76 MAN0443 P65 Issue 13 Aug 04 5701 Control System 05701 M 5001 A02279 CHAPTER 4 INSTALLATION INSTRUCTIONS ...
Страница 173: ...6 12 MAN0443 P65 Issue 13 Aug 04 5701 Control System 05701 M 5001 A02279 CHAPTER 6 OPERATING INSTRUCTIONS ...
Страница 209: ...9 4 MAN0443 P65 Issue 13 Aug 04 5701 Control System 05701 M 5001 A02279 CHAPTER 9 ORDERING INFORMATION ...