6 - 7
MAN0443.P65 Issue 13 Aug 04
5701 Control System
05701-M-5001 A02279
CHAPTER 6 - OPERATING INSTRUCTIONS
(2)
Push the
BEAD mA
push-button and the selected
channel card display will indicate the configured bridge
current. eg. 200mA.
(3)
Push the reject ( ) push-button or wait 30 seconds to
exit the
Bead mA
mode.
4.5
View Alarm Level Settings
The operation of the
ALARMS
push-button allows the viewing of the
alarm threshold point and alarm type (rising or falling) for each alarm
set point A1, A2 and A3.
To enter the alarm view operation, proceed as follows:
(1)
Push and hold the required channel card
RESET/
SELECT
push-button for approximately 1.5 seconds
until the selected icon appears on the channel display.
(2)
Push the
ALARMS
push-button and the selected
channel card display will indicate the A1 level alarm as
indicated opposite.
Note: The up arrow
A
indicates a rising alarm while the down
A
arrow
indicates a falling alarm.
(3)
Push the
ALARMS
push-button a second time and the selected
channel card display will indicate the A2 level alarm.
(4)
Push the
ALARMS
push-button a third time and the selected
channel card display will indicate the A3 level alarm.
(5)
Push the
ALARMS
push-button a fourth time and the selected
channel card display will indicate the STEL level alarm.
(6)
Push the
ALARMS
push-button a fifth time and the selected channel
card display will indicate the LTEL level alarm.
(7)
Further pushes of the
ALARMS
push-button will scroll through the
alarm level set points again. ie. A1, A2, A3, STEL and LTEL.
Note: Where an alarm function is disabled, the alarm threshold value
will be displayed as '
- - - -
' in the digital display.
(8)
Push the ( ) or ( ) push-buttons or wait 30 seconds to exit the
ALARMS
mode.
Содержание 5701
Страница 1: ...Sieger System 57 5701 Control System Operating Instructions ...
Страница 45: ...2 32 MAN0443 P65 Issue 13 Aug 04 5701 Control System 05701 M 5001 A02279 CHAPTER 2 SYSTEM DESCRIPTION ...
Страница 63: ...3 18 CHAPTER 3 CONTROLS AND FACILITIES MAN0443 P65 Issue 13 Aug 04 5701 Control System 05701 M 5001 A02279 ...
Страница 139: ...4 76 MAN0443 P65 Issue 13 Aug 04 5701 Control System 05701 M 5001 A02279 CHAPTER 4 INSTALLATION INSTRUCTIONS ...
Страница 173: ...6 12 MAN0443 P65 Issue 13 Aug 04 5701 Control System 05701 M 5001 A02279 CHAPTER 6 OPERATING INSTRUCTIONS ...
Страница 209: ...9 4 MAN0443 P65 Issue 13 Aug 04 5701 Control System 05701 M 5001 A02279 CHAPTER 9 ORDERING INFORMATION ...