8 - 5
MAN0443.P65 Issue 13 Aug 04
5701 Control System
05701-M-5001 A02279
CHAPTER 8 - SPECIFICATION
5.2
Single Channel Control Card
Four-Part Liquid Display:
Analogue Display:
25 segment.
Digital Display:
Four character.
Message Display:
Four character.
Icon Section:
Power On/Card Select.
LEDs:
A1, A2, A3 gas alarms.
Fault and Inhibit.
Push-Button:
Alarm Reset/Card Select.
Alarm Setting Point
Resolution:
In 1% fsd steps.
Display/Alarm Point:
Linearity:
±
1% fsd.
Repeatability:
±
1% fsd.
Remote Facilities:
Inhibit/Alarm Reset.
Remote Inhibit / Reset Inputs
Active For Inputs:
More than 2V.
Maximum Input Voltage:
32V.
Maximum Input Current:
5mA.
Power Consumption:
Catalytic:
3.75W (typical).
(Includes Catalytic Sensor).
4 - 20mA:
3.25W (typical).
DC Supply:
18V to 32V dc.
Electronic Drift:
Less than
±
2% / 6 months.
Dimensions:
Height:
112mm.
Width:
25mm.
Depth:
170mm.
Weight:
165g.
Содержание 5701
Страница 1: ...Sieger System 57 5701 Control System Operating Instructions ...
Страница 45: ...2 32 MAN0443 P65 Issue 13 Aug 04 5701 Control System 05701 M 5001 A02279 CHAPTER 2 SYSTEM DESCRIPTION ...
Страница 63: ...3 18 CHAPTER 3 CONTROLS AND FACILITIES MAN0443 P65 Issue 13 Aug 04 5701 Control System 05701 M 5001 A02279 ...
Страница 139: ...4 76 MAN0443 P65 Issue 13 Aug 04 5701 Control System 05701 M 5001 A02279 CHAPTER 4 INSTALLATION INSTRUCTIONS ...
Страница 173: ...6 12 MAN0443 P65 Issue 13 Aug 04 5701 Control System 05701 M 5001 A02279 CHAPTER 6 OPERATING INSTRUCTIONS ...
Страница 209: ...9 4 MAN0443 P65 Issue 13 Aug 04 5701 Control System 05701 M 5001 A02279 CHAPTER 9 ORDERING INFORMATION ...