MAN0443.P65 Issue 13 Aug 04
5701 Control System
05701-M-5001 A02279
CHAPTER 4 - INSTALLATION INSTRUCTIONS
4 - 67
16.
DC POWER CONNECTIONS
16.1
General
CAUTION
The ratings of power supplies should be checked by calculating a
system power budget as outlined in Section 5.
IMPORTANT
The System 57 must be earthed
DC power is connected to the System 57 via the DC Input Card
terminal block TB1.
The DC Input Card provides diode isolation to permit the connection of
two separate power supplies. eg. A mains derived dc power supply
and battery backup dc supply. Note that current will be drawn from the
supply input with the highest voltage and in some circumstances
current will be shared between the two inputs. Each of the two inputs
have twin +24V and 0V terminals for easy through power connection
or paralleling of input sources.
A fused +24V output, which is the combination of both dc inputs, is
provided for powering ancillary devices.
Site DC Supply and Auxiliary Battery Backup DC Power Supply
Connections, With Through Wiring
System Earth
Aux Battery
24V DC Supply
Aux Battery
Through Wiring
Site PSU
Through Wiring
Site PSU
24V DC Nominal
24V Output to
Ancillary Equipment
FS1
10A
12
11
10
9
8
7
6
5
4
3
2
1
TB1
Содержание 5701
Страница 1: ...Sieger System 57 5701 Control System Operating Instructions ...
Страница 45: ...2 32 MAN0443 P65 Issue 13 Aug 04 5701 Control System 05701 M 5001 A02279 CHAPTER 2 SYSTEM DESCRIPTION ...
Страница 63: ...3 18 CHAPTER 3 CONTROLS AND FACILITIES MAN0443 P65 Issue 13 Aug 04 5701 Control System 05701 M 5001 A02279 ...
Страница 139: ...4 76 MAN0443 P65 Issue 13 Aug 04 5701 Control System 05701 M 5001 A02279 CHAPTER 4 INSTALLATION INSTRUCTIONS ...
Страница 173: ...6 12 MAN0443 P65 Issue 13 Aug 04 5701 Control System 05701 M 5001 A02279 CHAPTER 6 OPERATING INSTRUCTIONS ...
Страница 209: ...9 4 MAN0443 P65 Issue 13 Aug 04 5701 Control System 05701 M 5001 A02279 CHAPTER 9 ORDERING INFORMATION ...