MAN0443.P65 Issue 13 Aug 04
5701 Control System
05701-M-5001 A02279
CHAPTER 4 - INSTALLATION INSTRUCTIONS
4 - 57
IS Series 2000 Toxic Sensor With Double Safety Barrier
Relay/Field Interface Card
05701-A-0326
05701-A-0327
05701-A-0328
05701-A-0329
05701-A-0330
Single Channel Control Card 4 - 20mA 05701-A-0301
Fitted With 4 - 20mA Sensor Drive 05701-A-0283
1
2
Double IS
Safety Barrier
x 3
S
01
Arrows Indicate Direction of
Loop Current Flow
Two Core Screened Cable
GND
IS Series 2000
Toxic Sensor
Terminal Block
Earth Stud
If the measuring resistance is in the negative supply line, a double
safety barrier must be used.
Cabinet
Protective
Earth
x 3
28
25
27
29
NS
GND
Link Positions
LK1
LK4
LK10
LK13
WARNING
Do not short the S and NS input lines since this
may cause damage to the Control Card input
circuit.