CODESYS‐V3 Soft PLC (WGX001 only)
PMX
A4354-2.2
HBM: public
347
18.7 Task configuration
The following task types can be selected under Main
Task:
S
Cyclic
The task is started asynchronously to the measured
values.
The interval must be at least 4 ms
, that is
the shortest possible resolution.
S
External - Measval Event
The task is started synchronously with the acquired
measured values. The calling frequency is set in the
"System Options" dialog. Default: 1,200 Hz, i.e. at a
sampling rate of 19,200 Hz, the task is started after
every 16th measured value.
S
External - SystemEvent
The task is started when a PMX system event occurs
(this event is also displayed in the device system log).
The number of the event is delivered within the task
by the library function getSystemeventNo (see chap
ter 18.10). .
The system events can be called up via the browser
with the device path http://<pmx devicename>/data/
systemevent.xml.
Where possible, only select these task types
Содержание PX401
Страница 1: ...Operating Manual English PMX...
Страница 104: ...Electrical connections PMX 104 A4354 2 2 HBM public PMX...
Страница 136: ...Startup 136 A4354 2 2 HBM public PMX This takes you to the device overview Now you can measure make settings and observe...
Страница 141: ...Startup PMX A4354 2 2 HBM public 141 Network settings...
Страница 238: ...Internal calculation channels 238 A4354 2 2 HBM public PMX Appendix Details of the glyphs in example A...
Страница 239: ...Internal calculation channels PMX A4354 2 2 HBM public 239...
Страница 241: ...Internal calculation channels PMX A4354 2 2 HBM public 241...
Страница 246: ...Internal calculation channels 246 A4354 2 2 HBM public PMX...
Страница 264: ...Internal calculation channels 264 A4354 2 2 HBM public PMX...
Страница 272: ...Parameter sets measurement programs 272 A4354 2 2 HBM public PMX...
Страница 295: ...Communication with a control system PMX A4354 2 2 HBM public 295...
Страница 297: ...Communication with a control system PMX A4354 2 2 HBM public 297...
Страница 300: ...Communication with a control system 300 A4354 2 2 HBM public PMX...
Страница 376: ...CODESYS V3 Soft PLC WGX001 only 376 A4354 2 2 HBM public PMX...
Страница 378: ...CODESYS V3 Soft PLC WGX001 only 378 A4354 2 2 HBM public PMX...
Страница 381: ...CODESYS V3 Soft PLC WGX001 only PMX A4354 2 2 HBM public 381...
Страница 392: ...CODESYS V3 Soft PLC WGX001 only 392 A4354 2 2 HBM public PMX Dialog Updating the PMX device...
Страница 489: ...Object directory PMX A4354 2 2 HBM public 489...
Страница 523: ...Diagnosis and maintenance PMX A4354 2 2 HBM public 523 Network settings...