7
Table 5
Switch dimensions and rack requirements
Model
Chassis dimensions
Rack requirements
S12510-X
AC
•
Height
—930 mm (36.61 in)/21 RU
•
Width
—440 mm (17.32 in)
•
Depth
—1018 mm (40.08 in)
{
830 mm (32.68 in) for the chassis
{
75 mm (2.95 in) for the cable
management brackets and 88 mm
(3.46 in) for the plastic panels at the
chassis front
{
100 mm (3.94 in) for the power cord
brackets at the chassis rear
•
1.1 m (3.61 ft) or 1.2 m (3.94 ft) in depth
(recommended)
•
A minimum of 95 mm (3.74 in) between
the front rack posts and the front door.
•
A minimum of 935 mm (36.81 in)
between the front rack posts and the
rear door.
NOTE:
If the distance between the front rack posts
and the front door does not meet the
requirement, do not install plastic panels and
ensure a minimum distance of 80 mm (3.15
in) between the front rack posts and the front
door.
S12510-X
DC
•
Height
—930 mm (36.61 in)/21 RU
•
Width
—440 mm (17.32 in)
•
Depth
—950 mm (37.40 in)
{
830 mm (32.68 in) for the chassis
{
75 mm (2.95 in) for the cable
management brackets and 88 mm
(3.46 in) for the plastic panels at the
chassis front
{
32 mm (1.26 in) for the fan tray
handles at the chassis rear
•
1.1 m (3.61 ft) or 1.2 m (3.94 ft) in depth
(recommended)
•
A minimum of 95 mm (3.74 in) between
the front rack posts and the front door.
•
A minimum of 865 mm (34.06 in)
between the front rack posts and the
rear door.
NOTE:
If the distance between the front rack posts
and the front door does not meet the
requirement, do not install plastic panels and
ensure a minimum distance of 80 mm (3.15
in) between the front rack posts and the front
door.
S12516-X
AC
•
Height
—1018 mm (40.08 in)/23 RU
•
Width
—440 mm (17.32 in)
•
Depth
—1023 mm (40.28 in)
{
830 mm (32.68 in) for the chassis
{
93 mm (3.66 in) for the cable
management brackets at the chassis
front
{
100 mm (3.94 in) for the power cord
brackets at the chassis rear
•
1.1 m (3.61 ft) or 1.2 m (3.94 ft) in depth
(recommended)
•
A minimum of 100 mm (3.94 in)
between the front rack posts and the
front door.
•
A minimum of 935 mm (36.81 in)
between the front rack posts and the
rear door.
S12516-X
DC
•
Height
—1018 mm (40.08 in)/23 RU
•
Width
—440 mm (17.32 in)
•
Depth
—955 mm (37.60 in)
{
830 mm (32.68 in) for the chassis
{
93 mm (3.66 in) for the cable
management brackets at the chassis
front
{
32 mm (1.26 in) for the fan tray
handles at the chassis rear
•
1.1 m (3.61 ft) or 1.2 m (3.94 ft) in depth
(recommended)
•
A minimum of 100 mm (3.94 in)
between the front rack posts and the
front door.
•
A minimum of 865 mm (34.06 in)
between the front rack posts and the
rear door.
Содержание S12500-X
Страница 35: ...26 Figure 20 Grounding the switch through the RTN wire of the DC power module...
Страница 80: ...71 Figure 51 Replacing an LPU 1 1 Loosen the captive screw 2 Pull the ejector levers outward...
Страница 138: ...129 Figure 75 CXP fiber cable 1 Connector 2 Pull latch 1 2...
Страница 152: ...143 Figure 91 Cable routing from the left side for an S12510 X AC S12510 X DC switch...