41
3.
Holding both sides of the module, gently push the module into the port until it has firm contact with
.
4.
Fasten the captive screws.
5.
Connect the fiber to the module. For the installation procedure, see "
Figure 34
Installing a CFP module
(1) Gently push the module into the port
(2) Fasten the captive screws
1
2