Gree GMV6 DC Inverter VRF Units Service Manual
225
4.3.1 Mechanical Inspection
(1) Confirm that the unit Power is disconnected.
(2) Find the 4-way valve or solenoid valve, check whether the fixing screw is loose and whether the
valve and coil have any apparent exceptions.
4.3.2 Electrical Inspection
Compare the measured coil resistance with the normal coil resistance to check whether the coil is
damaged.
(1) Power off the unit. Remove the electrical appliance cover after the ODU stops.
Warning:
Electric shock
(2) Remove the electrical appliance cover and check whether the connecting terminal of the 4-way
valve or solenoid valve is firm.
(3) Disconnect the corresponding valve's coil terminal from the main board and use a multimeter to
measure the coil resistance.
(4) If the measured resistance does not match with that in the following table, the coil needs to be
replaced.
Coil
Bolt on
the main
board
Resistance (Ω)
Normal range
of deviation
ODU capacity (HP)
8, 10, 12
14, 16, 18
20, 22, 24
Main cooling 4-way
valve
CN23
2085
±10%
Oil-return solenoid
valve 1
CN24
2085
±10%
Oil-return solenoid
valve 2
CN25
—
2085
±10%
Low-temperature
oil-return solenoid
valve
CN26
2085
±10%
Subcooler solenoid
valve
CN27
1273
±10%
Gas bypass valve
CN30
2085
±10%
Содержание GMV-1015WM/G-U
Страница 212: ...Gree GMV6 DC Inverter VRF Units Service Manual 210 Models GMV 400WM G U GMV 450WM G U GMV 504WM G U...
Страница 229: ...Gree GMV6 DC Inverter VRF Units Service Manual 227 Models GMV 400WM G U GMV 450WM G U GMV 504WM G U...
Страница 234: ...Gree GMV6 DC Inverter VRF Units Service Manual 232...
Страница 264: ...Gree GMV6 DC Inverter VRF Units Service Manual 262...
Страница 325: ...Gree GMV6 DC Inverter VRF Units Service Manual 323 GMV 400WM G U GMV 450WM G U and GMV 504WM G U...
Страница 331: ...JF00304610...